FULL GAUGE GPHASELOGEP VOLTAGE MONITOR

Full Guage
The PhaseLoge plus is an instrument for monitoring and protection of electrical equipment for industrial, commercial and residential facilities. Through the method of True RMS* voltage measurement, the PhaseLoge plus also monitors power quality and protects mono / bi / three phase loads against: under and over voltage, angular asymmetry, modular asymmetry, phase loss and phase sequence inversionThe internal datalogger stores the voltages of each phase of the electrical grid during periods of time determined by the user. Time and date of each sample is stored as well (internal real-time clock). All functions of the PhaseLoge plus can be changed through the software SITRAD®, which can be acessed through the internet (computer/iOS/Android). This software is also used to retrieve the data stored in its datalogger.
The controller allows configuring the RS485 communication port for Modbus protocol. For more information, contact Full Gauge Controls Application Engineering at eng aplicacao@fullgauge.com.br. *True RMS: Real voltage value (Root Mean Square), values evaluated taking into consideration the contribution of the high frequency noise on the network (harmonic distortion). That's the real voltage being perceived by the connected load (i.e. motors, compressors, etc). Using this method, it is possible to accurately measure the voltage at any waveform, whereas the traditional methods are only able to measure correctly pure sine waveforms.

International Delivery (Outside of Trinidad & Tobago)
We deliver worldwide via courier or freight forwarder.
Most orders are shipped with UPS or DHL. If you have an account with a specified courier, please let us know your account details when you are placing the order.
For larger orders, we ship via ocean freight with our freight forwarder.
Delivery within Trinidad & Tobago)
All orders within Trinidad & Tobago will be delivered either by our in-house delivery service or via TTPost. Delivery is usually fulfilled locally within 0-2 business days.
For orders placed after 7am, delivery will be fulfilled on the following business day.
For orders placed before 7am, it’s possible that we can accommodate same-day delivery as our driver usually leaves our warehouse for daily deliveries between 7-8am.
If you require an item urgently, do let us know. We will do our best to accommodate your needs.
Returns
We do not facilitate international returns.
For local returns, only items returned within 14 days of their original shipment date in same as new condition and in the original packaging will be eligible for a refund or store credit with the original receipt. Restocking & sanitization fees will be charged upon return.
Help
Give us a shout if you have any other questions and/or concerns.
Email: info@servair.com
Phone:1(868)-658-1910 / 1911 / 2010
APPLICATION
• Energy quality monitoring
• Motors protection
• Electrical panels protection
• Other multiphase equipments protection
TECHNICAL SPECIFICATIONS
Power supply Phaselog E: 90~240Vac (50/60 Hz)
Phaselog EL: 12Vdc/350mA ± 10%
Monitoring voltage range 90 to 600 VRMS (phase voltages)
90 to 600 VRMS (line voltages)
Monitoring frequency range 35 to 80 Hz
Frequency of sampling 7 Khz
Error (25ºC) < 1% of full scale range
Resolution 1 Vac in all range
Maximum Current 3A / 250Vac
Operational Temperature 0 to 50°C
Operational Humidity 10 to 90% UR (without condensation)
Minimum delay to open load output relay in case of failure 1 s
Dimensions 76 x 34 x 77 mm - 2,99" x 1,34" x 3,03" (WxHxD)
Dimensions of the clipping for fixing of the instrument 71 ± 0,5 x 29 ± 0,5 mm - 2,79"±0,02 x 1,14"±0,02