AC Won't Start: Capacitor, Contactor or Compressor?
Test in cost order: capacitor, then contactor, then compressor. A capacitor is a few hundred dollars and ten minutes. A compressor is the most expensive part on the unit. Most “dead compressor” calls in Trinidad are a failed run capacitor, and the difference between the two diagnoses is one meter reading.
Here is the sequence, in the order that finds the fault for the least money.
The six tests, in order
| # | Test | Looking for | If it fails |
|---|---|---|---|
| 1 | Supply voltage at the disconnect | Nameplate voltage, both legs | Supply fault — stop, it is not the unit |
| 2 | Control voltage at the contactor coil | 24V when calling for cool | Thermostat, transformer or wiring |
| 3 | Run capacitor, out of circuit, discharged | Microfarads within tolerance of the printed rating | Replace the capacitor |
| 4 | Contactor contacts and pull-in | Clean closure, no pitting, no chatter | Replace the contactor |
| 5 | Compressor windings | Continuity C–S, C–R, and R–S = sum of the other two | Open or shorted winding |
| 6 | Winding to earth | High resistance to the shell | Compressor is earthed — replace |
Discharge the capacitor before touching it. A run capacitor holds a lethal charge after the power is off, and it does not care that the disconnect is pulled.
Reading the symptom before you open anything
| What it does | Most likely | Test first |
|---|---|---|
| Hums, does not start, trips after seconds | Run capacitor | 3 |
| Outdoor fan spins, compressor silent | Capacitor (dual, compressor side) | 3 |
| Compressor runs, outdoor fan does not | Capacitor (fan side) or fan motor | 3 |
| Loud buzz at the contactor, no pull-in | Contactor coil | 2, then 4 |
| Nothing at all, no indoor response | Supply or control circuit | 1, then 2 |
| Starts, runs briefly, cuts out repeatedly | Overload, charge, or airflow | 1 — then check the air side |
Two Trinidad-specific causes worth ruling out
Supply voltage. Dips and brownouts are hard on motors and capacitors. A compressor asked to start on low voltage draws heavily, heats, and trips its overload — presenting exactly like a failing compressor. Measure the supply under starting load, not at rest, before condemning anything expensive.
Salt and moisture in the outdoor cabinet. Coastal installations corrode contactor contacts and terminal connections. Pitted contacts cause voltage drop that shows up as a hard-starting compressor. Look at the contacts before assuming the motor is at fault.
Parts, once you have found it
| Part | Where |
|---|---|
| Capacitors | Electrical & In-Line Components |
| Contactors | Electrical & In-Line Components |
| Relays | Electrical & In-Line Components |
| Transformers | Electrical & In-Line Components |
| Overloads | Compressors & Accessories |
| Compressors | Compressors & Accessories |
Match a capacitor on both microfarad rating and voltage rating. A higher voltage rating is acceptable; a lower one is not, and a wrong microfarad value will run the motor hot and shorten its life even though the unit appears to work.
Counter: 1 (868) 658-1910. WhatsApp a nameplate photo to 1 (868) 658-1911.
Frequently Asked Questions
How do I know if a capacitor is bad without a meter that reads microfarads?
You largely do not, and guessing is how good capacitors get replaced and bad ones get missed. A visibly bulged top or leaking case is a definite failure, but a capacitor can be well out of tolerance while looking perfect. A meter with a capacitance range is the only reliable test, and it is inexpensive relative to one wrongly-condemned compressor. Test it out of circuit and discharged.
The compressor windings read fine but it still will not start. What else?
Work through, in order: supply voltage under starting load, the run capacitor's actual measured value, the contactor's contact condition, and whether the system is equalising between starts. A compressor asked to restart against unequalised head pressure will stall even when it is electrically sound. Mechanical seizure is real but it is the last conclusion, not the first.
Is it worth replacing a compressor or should the unit be replaced?
Weigh the compressor and labour against the age and condition of the rest of the system. If the coils are corroded, the unit is on an obsolete refrigerant, or it has already had major work, the money is usually better spent on replacement. If the system is otherwise sound and the compressor failed from an identifiable, fixable cause — a supply fault or a failed capacitor left running — replacing it is reasonable, provided the original cause is corrected at the same time.