AC Won't Start: Capacitor, Contactor or Compressor?

Published in: 8 Sept 2026
AC Won't Start: Capacitor, Contactor or Compressor?

Test in cost order: capacitor, then contactor, then compressor. A capacitor is a few hundred dollars and ten minutes. A compressor is the most expensive part on the unit. Most “dead compressor” calls in Trinidad are a failed run capacitor, and the difference between the two diagnoses is one meter reading.

Here is the sequence, in the order that finds the fault for the least money.

The six tests, in order

#TestLooking forIf it fails
1Supply voltage at the disconnectNameplate voltage, both legsSupply fault — stop, it is not the unit
2Control voltage at the contactor coil24V when calling for coolThermostat, transformer or wiring
3Run capacitor, out of circuit, dischargedMicrofarads within tolerance of the printed ratingReplace the capacitor
4Contactor contacts and pull-inClean closure, no pitting, no chatterReplace the contactor
5Compressor windingsContinuity C–S, C–R, and R–S = sum of the other twoOpen or shorted winding
6Winding to earthHigh resistance to the shellCompressor is earthed — replace

Discharge the capacitor before touching it. A run capacitor holds a lethal charge after the power is off, and it does not care that the disconnect is pulled.

Reading the symptom before you open anything

What it doesMost likelyTest first
Hums, does not start, trips after secondsRun capacitor3
Outdoor fan spins, compressor silentCapacitor (dual, compressor side)3
Compressor runs, outdoor fan does notCapacitor (fan side) or fan motor3
Loud buzz at the contactor, no pull-inContactor coil2, then 4
Nothing at all, no indoor responseSupply or control circuit1, then 2
Starts, runs briefly, cuts out repeatedlyOverload, charge, or airflow1 — then check the air side

Two Trinidad-specific causes worth ruling out

Supply voltage. Dips and brownouts are hard on motors and capacitors. A compressor asked to start on low voltage draws heavily, heats, and trips its overload — presenting exactly like a failing compressor. Measure the supply under starting load, not at rest, before condemning anything expensive.

Salt and moisture in the outdoor cabinet. Coastal installations corrode contactor contacts and terminal connections. Pitted contacts cause voltage drop that shows up as a hard-starting compressor. Look at the contacts before assuming the motor is at fault.

Parts, once you have found it

Match a capacitor on both microfarad rating and voltage rating. A higher voltage rating is acceptable; a lower one is not, and a wrong microfarad value will run the motor hot and shorten its life even though the unit appears to work.

Counter: 1 (868) 658-1910. WhatsApp a nameplate photo to 1 (868) 658-1911.

Frequently Asked Questions

How do I know if a capacitor is bad without a meter that reads microfarads?

You largely do not, and guessing is how good capacitors get replaced and bad ones get missed. A visibly bulged top or leaking case is a definite failure, but a capacitor can be well out of tolerance while looking perfect. A meter with a capacitance range is the only reliable test, and it is inexpensive relative to one wrongly-condemned compressor. Test it out of circuit and discharged.

The compressor windings read fine but it still will not start. What else?

Work through, in order: supply voltage under starting load, the run capacitor's actual measured value, the contactor's contact condition, and whether the system is equalising between starts. A compressor asked to restart against unequalised head pressure will stall even when it is electrically sound. Mechanical seizure is real but it is the last conclusion, not the first.

Is it worth replacing a compressor or should the unit be replaced?

Weigh the compressor and labour against the age and condition of the rest of the system. If the coils are corroded, the unit is on an obsolete refrigerant, or it has already had major work, the money is usually better spent on replacement. If the system is otherwise sound and the compressor failed from an identifiable, fixable cause — a supply fault or a failed capacitor left running — replacing it is reasonable, provided the original cause is corrected at the same time.